Home / Blog / Partial Discharge Measurement Pd To Judge The Winding Of Low Voltage Machines
02-06-2025
Partial discharge measurement (PD) on low-voltage machines
With a partial discharge (PD) measurement you assess the winding insulation of low-voltage machines, especially when they run on frequency converters. You read what partial discharge is and what PDIV and RPDIV mean.
Introduction to partial discharge measurement
Partial discharge measurement (PD) to assess the windings of low-voltage machines for suitability for frequency converters and general insulation strength
Introduction
Partial discharge tests have become increasingly important for assessing the insulation of electrical machines in recent years. This is particularly due to the huge increase in frequency converters for motor control. SCHLEICH’s years of experience show that many users talk about partial discharge testing, but have no precise idea of what partial discharge exactly means.
This description is intended to shed some light on the test method. It is less a scientific explanation than a generally understandable description of the measurement method and its applications.
What is partial discharge?
The typical “complete breakdown” is known from the classic high voltage AC test.
How much leakage current is too much?
Figure 1 – Damaged conductor near the laminated core
Electrical machines are usually rated as follows: “The machine must not malfunction or have excessive leakage current.”
The question “What is too much current during the high-voltage test?” is no longer so simple to answer.
Leakage current, crackling and partial discharge
Figure 2 – Breakdown or capacitive leakage current
In manufacturing, the maximum allowable current during the high-voltage test can be determined and specified from comparative measurements. However, this current limit is usually not available to the person taking measurements during repairs. Depending on the capacity of the insulation in the machine, the current is low for smaller electrical machines and correspondingly higher for larger ones.
Experienced professionals often feel that too much leakage current runs through the machine and/or that crackling noises occur during the high-voltage test. In such cases, there is no complete failure; partial discharge effects occur. These need to be reliably measured and analysed.
In the case of partial discharge, there is only a breakdown in part of the insulation in the sense of the word “partial…”.

Figure 3 – Partial discharge at a wire with good enamel insulation close to the laminated core
Weak spot in the insulation
Figure 4 – Partial discharge between touching windings
This partial area is a partial insulation weakness or bad area.
How partial discharge occurs
Figure 5 – partial discharge in a highly loaded section
This weak point is overloaded during electric motor operation or during the high voltage test. The weak point cannot withstand this increased load and, as a result, partial breakdown occurs in this partial area. This partial breakdown is called partial discharge. However, the remaining insulation still withstands the increased voltage load, so no complete breakdown occurs.
The following diagram illustrates the basic structure of insulation. High voltage is applied between two electrical conductors (e.g. winding and winding).
Consequences of partial discharge and the test voltage
Figure 6 – Partial discharge illustrated using an equivalent circuit diagram
The electrical conductors are separated from each other by the insulation. In a completely homogeneous case, the insulation can be thought of as a large capacitor (CIso). However, due to a defect in the insulation, there may be spatial areas that are locally overloaded by a high electric field strength (Cair). This is shown in the centre of the diagram. Partial discharge occurs in this overloaded subarea.
The consequence of this partial discharge is a slow but steady damage of the still functional parts of the insulation system. Exactly according to the principle of “constant dripping hollows out the stone”, the permanent partial discharges continuously lead to an enlargement of the damaged area. This inevitably leads to the still functional insulation soon no longer withstanding the load. This leads to a complete failure and thus a faulty electrical machine.
For low-voltage machines with a PD-free insulation system (Type I, IEC 60034-18-41), the aim must be to prevent partial discharges. There it is only a matter of time before even small partial discharges destroy a machine.
Partial discharge is a voltage-dependent physical effect. If the voltage increases, at some point partial discharge will also occur. The only question is how high the test voltage should be. The answer lies in the application of the electrical machine. Depending on that, the test voltage for partial discharge should be chosen.
Electrical machines on industrial networks without frequency converters
An electrical machine that operates directly on the three-phase mains without a frequency converter is loaded only by the mains voltage and occasionally by switching spikes. In this application, it makes no sense to test the machine with very high test voltages for freedom from partial discharge.
High-voltage machines
High-voltage machines logically need a test voltage adapted to the high operating voltage. Their insulation system (Type II, with mica) is PD-resistant. So you do not test for the absence of partial discharge, but assess the PD level and its trend (IEC 60034-27-1). The test voltage must therefore also be selected accordingly high.
Electrical machines on industrial networks with frequency converters
Electrical machines used on frequency converters should be tested for the absence of partial discharge with a higher test voltage. Why is this necessary? It is not immediately clear why a machine with a frequency converter needs to be tested with a higher test voltage. The following question can be asked How can a high voltage occur on electrical machines with a frequency converter? The answer lies in the basic functional operation of the frequency converter. In a variable speed drive, the single-phase or three-phase AC voltage supplied is first rectified and then smoothed and stored in correspondingly large capacities. This intermediate circuit with smoothing capacitor is often referred to as the DC link. The theoretical maximum DC voltage level in the DC link is the result of the RMS value of the mains voltage multiplied by √2. On a 400 V network this is about 565 V, under load about 540 V.
Basic circuit of the frequency converter
Figure 7 – Basic circuit of the frequency inverter
Modern high-speed electronic switches are used to convert the stored DC voltage back into (pulsed) AC voltage. The result is not a pure sine wave, but a signal composed of square-wave pulses.
Pulse width modulation and steep edges
Figure 8 – Sinusoidal signal modelled from square wave pulses
The amplitude of the square-wave signal cannot be changed because the electronic switches switch the DC voltage to the electric motor or not.
However, the pulse duration (duty cycle of the electronic switches) can be varied by the inverter. By varying the pulse width, a sine wave is simulated. This process is called pulse width modulation (PWM).
In recent years, the almost rectangular pulses have acquired an increasingly steeper edge. This is the aim of semiconductor manufacturers of electronic switches to keep the power loss in the switch as low as possible during the switching phase. This is because a large part of the losses (heating of the semiconductors) occurs during the switching phase. The faster the electronic switch switches, the lower the losses and the lower the cooling effort in an AC drive. From an AC drive manufacturer’s point of view, steep edges are therefore the goal of development.
From the point of view of electrical machinery manufacturers, high steep edges are a major problem. The reason: steep edges lead to voltage spikes during switching (1).
Voltage peaks at the start of the winding
Figure 9 – Rectangular signal with steep edges and surge peaks
This is because in electrical engineering, square-wave signals basically exist only on the basis of composite sine-wave signals of different frequencies and different amplitudes. The steeper the slope of the square wave, the higher the frequency of the sine wave signals used to “mimic” the slope. The amplitude of these higher harmonics does decrease, though. The overvoltage at the motor terminals is mainly caused by reflection in the cable between converter and motor. It can reach about 2 × UDC and increases with cable length, up to a critical length.
If the high-slope signals are now connected to a coil (i.e. the electric motor), the high-frequency components of the square-wave signal are filtered out at the coil. These high-frequency signal components drop out at the first windings of the winding. As a result, the winding is particularly heavily loaded at the beginning during frequency converter operation. The following diagram clearly shows the relationship between the steepness of the high edges and the resulting voltage drop across the winding of a phase.
Overvoltage and rise time
Figure 10 – Voltage curve across the winding as a function of flank steepness
There is a very good article on the level of the overvoltage pulse (10). Here, a correlation between the overvoltage pulse and the rise time is determined. The value of the resulting overvoltage is multiplied by the DC link voltage UDC to obtain the absolute value of the overvoltage. Depending on the rise time, that article defines 4 voltage ranges (I to IV). The normative classification is in IEC 60034-18-41, with classes A to D (IVIC).
How do you measure partial discharge?
Figure 11 – Voltage ranges I – IV with overvoltage factor as a function of rise time
Measurement methods: current pulse or high-frequency measurement?
We mentioned at the beginning that partial discharge occurs at weak points in the insulation when the load becomes too high. Since the current of the partial discharges is negligible compared with the capacitive current, and the measured leakage current therefore hardly changes, the question arises, “How can partial discharge be measured?”. If something discharges and there is still an external voltage on the device under test, charge will immediately reappear. This means that partial discharge can be measured directly via charging. The charge pulse is only a few nanoseconds wide. It is a very fast, high-frequency current pulse. Measurement technology must therefore be able to detect these fast pulses.
PD coupler and electromagnetic signal
Figure 12 – Partial discharge test on motor/generator or stator with coupling for the high-frequency current pulse
The PD coupler is integrated into the device or can be simply connected to the test leads of the device under test.
The discharge signal is emitted electromagnetically in parallel with the discharge. This is similar to an electric spark or a lightning flash. The spark generates a very broadband high-frequency signal, which in principle can be recognised with a radio (world receiver).
Current pulse or antenna measurement
Figure 13 – Partial discharge test on stator with high-frequency current pulse antenna
SCHLEICH has been using current pulse and high-frequency antenna measurements for many years. Both measurement methods have advantages and disadvantages. However, neither measurement method is superior to the other.
The disadvantage of the current pulse measurement method is that it can be affected by external interference. External interference can lead to the measurement of an apparent partial discharge on an electrical machine. This drawback can be greatly reduced, but not completely eliminated, by using special filters.
High-frequency measurement of the electromagnetic wave using a special antenna has the advantage that, depending on the wisely chosen, very high frequency range, the influences of external disturbances are no longer present or their effects are reduced. Choose the measuring frequency range outside the bands of, for example, radio transmitters and mobile phones. The disadvantage of this measurement method is that a completely mounted motor hardly passes any high-frequency signals. The motor housing acts as a Faraday cage for the winding inside.
For these reasons, SCHLEICH recommends both measurement methods. The combination of both measurement methods is ideal, so one or the other can be used depending on the application.
Online or offline measurements?
A distinction is made between these two operating states of the electrical machine. In online measurements, the machine is in service, supplied by the mains or a converter. In offline measurement, the machine is stationary.
SCHLEICH currently uses the partial discharge test as an offline measurement. It can be measured offline during repairs in the winding shop or when the machine is stationary for maintenance purposes. The disadvantage of offline use is that special insulation problems that occur due to centrifugal or magnetic forces generated during rotation cannot be measured. The advantage of offline measurement is that it is easier to analyse partial discharge effects, which are not strongly superimposed and affected by interference, for example when using a variable speed drive.
Offline measurement takes place in combination with the high voltage test or the peak voltage test.
High-voltage surge test as a prerequisite for PD measurement?
The partial discharge test can be performed in combination with a high-voltage or peak-voltage test. Both test methods serve as basic tests to stimulate partial discharge.
The AC high voltage test measures the dielectric strength and also the partial discharge between the windings and/or the winding to earth (housing).
The Surgetest PD mainly “looks” directly into the winding (from winding to winding) to detect weak spots in the insulation there. That is its strength. In addition, it also measures partial discharge.
However, under certain conditions, partial discharge combined with overvoltage testing is less sensitive to weak points between the winding and earth or between the phases. Both test methods are thus justified to reliably measure the partial discharge of a machine.
Therefore, SCHLEICH supplies testers for both methods. A combination of both methods is optimal.
The physical unit pC (pico Coulomb)
The unit of charge is the coulomb (C). Partial discharge is expressed in pC (apparent charge). The equation for charge is: Q = C * U. The charge is therefore the product of the capacity (which stores the charge) and the voltage level applied to it.
Partial discharge is measured in the range of about 1pC to some 1000pC. 1pC is very small. The voltage of 1 Volt on a capacitance of 1 picoFarad results in 1 picoCoulomb charge!
In a surge PD test (IEC TS 61934, IEC 60034-18-41) it is in practice not necessary to use measuring equipment with a picoCoulomb display. It is sufficient to use sensitive measurement technology to recognise whether partial discharge is present or not. The determination of the inception and extinction voltage of the partial discharge is more important than the absolute measurement value of the partial discharge in the unit picoCoulomb.
This is why SCHLEICH produces the partial discharge testers without the picoCoulomb display. For an AC PD measurement according to IEC 60270, calibration in pC is required.
Inception and extinction voltage
The inception voltage (PDIV), the repetitive inception voltage (RPDIV), the extinction voltage (PDEV) and the repetitive extinction voltage (RPDEV) are often measured to assess insulation. The high voltage (whether AC voltage or surge voltage) is continuously increased from a starting value to a maximum value.
Once partial discharge starts at a certain voltage, this is defined as the partial discharge inception voltage (PDIV). The high voltage is then reduced until the partial discharge stops again. This value is then the partial discharge extinction voltage (PDEV). With surge voltage, partial discharge counts as repetitive when it occurs in at least 5 of 10 pulses. RPDIV and RPDEV therefore only apply to surge voltage.
PDIV = Partial Discharge Inception Voltage
RPDIV = Repetitive Partial Discharge Inception Voltage
RPDEV = Repetitive Partial Discharge Extinction Voltage
PDEV = Partial Discharge Extinction Voltage
Assessing inception and extinction voltage
Figure 14 – Inception voltage and extinction voltage of partial discharge
A good, intact insulation system is characterised by both voltage values being at a high level. The basic rule is: “The higher, the better”. However, the voltage values should be at least higher than the level of possible voltage spikes that occur during operation. The standards specify guide values for this. IEC 60034-18-41 multiplies the expected peak voltage by factors for temperature, ageing and safety.
High-voltage testers AC high voltage and PD
This test technology has been part of SCHLEICH winding testers for motor production for years.
Features of the MTC2 and MTC3
Figure 15 – Partial discharge during high voltage AC testing
The MTC2 and MTC3 testers have the following typical features
Partial discharge test according to national and international standards for surge PD (IEC TS 61934, IEC 60034-18-41)
Electronic sinusoidal high voltage source
Adjustable high voltage with very fine voltage resolution
Adjustable frequency of high voltage to allow measurements for different application areas and different markets
Capacitive decoupling of the partial discharge pulse
Inductive decoupling of the partial discharge pulse
High-frequency measurement of the partial discharge pulse in the gigahertz range with antenna
Automatic determination of the inception and extinction voltage
Automatic peak value determination of partial discharge
Automatic determination of partial discharge sum
Surge testers with partial discharge
This test technology has been part of SCHLEICH winding testers for motor production for years. Many well-known motor manufacturers rely on this SCHLEICH method.
Partial discharge during the surge test
Figure 16 – Partial discharge during Surge test with automatic inception and extinction voltage measurement
Capacitive decoupling at 150 ns rise time
Figure 17 – 150 ns rise time with capacitive decoupling of partial discharge
Experience, conclusion and references
Figure 18 – 150 ns rise time with high-frequency antenna measurement of partial discharge
Experience and conclusion
SCHLEICH has years of experience with the partial discharge test at motor manufacturers worldwide, and that experience is very positive. It is a test method that uniquely detects both manufacturing defects and ageing effects. The test method is therefore of great importance for manufacturing as well as repair and maintenance. SCHLEICH’s experience covers machines and generators from 100 W to 4 MW.
On fully assembled machines, where the housing shields the high-frequency signal, measuring the current pulse in the supply lines is a good alternative to high-frequency measurement with an antenna. Keep in mind that current pulse measurement is more sensitive to external interference. Current pulse measurement allows partial discharge measurements to be made reliably on assembled electrical machines. The user does not have to worry about the ideal antenna placement.
Furthermore, SCHLEICH offers an excellent combination of partial discharge measurements based on alternating high voltage and peak voltage worldwide.
Switching between the different winding connections of the electrical machine is fully automatic. The maximum test voltage differs per model: according to SCHLEICH, the MTC3 does surge up to 15 kV and AC up to 6 kV.
All SCHLEICH devices are SCHLEICH’s own developments and are produced entirely in-house. Based on 25 years of experience in peak voltage testing, SCHLEICH produces the test equipment in Germany, at its own site in Hemer. IONIO supplies the SCHLEICH testers in the Netherlands.
The partial discharge test is available on the MTC2 R7 surge tester and the MTC3 universal motor tester.
Literature / References
Some information has been taken from the following sources:
(1) Paper No. PCIC-2004-27: “PARTIAL DISCHARGE INCEPTION TESTING ON LOW VOLTAGE MOTORS”, IEEE, 2004
(2) IEC/TS 60034-18-41 ed1.0: „Rotating electrical machines – Part 18-41: Qualification and type tests for Type I electrical insulation systems used in rotating electrical machines fed from voltage converters“; 2006
(3) IEC 60034-18-42:2017+A1:2020: Rotating electrical machines – Part 18-42: Qualification and acceptance tests for partial discharge resistant electrical insulation systems (Type II) used in rotating electrical machines fed from voltage converters“
(4) IEC 60034-27-1:2017: „Rotating electrical machines – Part 27-1: Off-line partial discharge measurements on the winding insulation“
(5) IEC/TS 61934 ed 2.0: „Electrical insulating materials and systems – Electrical measurement of partial discharges (PD) under short rise time and repetitive voltage impulses“; 2011
(6) VDE 0530-18-41: Drehende elektrische Maschinen Teil 18-41: Qualifizierung und Qualitätsprüfung für teilentladungsfreie elektrische Isoliersystem (Typ I) in drehenden elektrischen Maschinen, die von Spannungsumrichtern gespeist werden“; 2021
(7) VDE 0530-18-42: „Drehende elektrische Maschinen Teil 18-42: Qualifizierungs- und Abnahmeprüfungen teilentladungsresistenter Isoliersysteme (Typ II) von drehenden elektrischen Maschinen, die von Spannungsumrichtern gespeist werden“; 2011
(8) VDE 0530-27: „Drehende elektrische Maschinen Teil 27: Off-Line Teilentladungsmessungen an der Statorwicklungsisolation drehender elektrischer Maschinen“; 2011
(9)R.H.Rehder – W.J.Jackson-B.J.Moore; Designing Refiner Motors to Withstand Switching Voltage Transients
(10) M. Tozzi – A. Cavallini – G.C.Montanari; „Monitoring Off-Line and On-Line PD Under Impulsive Voltage on Induction Motors – Part 1: Standard Procedure“; 2010
(11) M. Tozzi – A. Cavallini – G.C.Montanari; „Monitoring Off-Line and On-Line PD Under Impulsive Voltage on Induction Motors – Part 2: Testing“; 2010
Gijsbert at IONIO is here to help you.
At IONIO, we not only supply advanced testing and measurement systems, but also offer clear and expert advice to optimise the testing of your product.
Find out how we can improve your business processes. A consultation can be scheduled in no time!
Personal advice
From our specialists
Advice, a quote or rental? We are happy to help.