Home / Products / Cibre L6 6 Contact Circuit Breaker Timer

CIBRE‑L6 serie – 6‑contact Circuit Breaker Timer

The CIBRE-L6 is the professional circuit breaker timer for three-phase circuit breakers — with 6 independent contact inputs you measure all three phases simultaneously in a single run. You perform open, close, and combined switching cycles in accordance with IEC 62271-100 and IEEE C37.09, with a timing accuracy of ±0.05% rdg ± 0.1 ms. The built-in 2.25″ thermal printer and optional Li-ion battery make the CIBRE-L6 fully field-ready: from substation commissioning to periodic inspection, even without mains power.

ConsultationRequest a quoteBrochure

Applications

  • Commissioning of three-phase circuit breakers: simultaneous contact timing of all three phases in one run
  • Periodic inspection in accordance with IEC 62271-100: document open and close times and detect deviations
  • Factory Acceptance Test (FAT): contact timing verification including resistive contacts
  • Substation commissioning: field use without mains power via Li-ion battery option (IP67 case)
  • Analysis of O, C, O-C, C-O, and O-C-O cycles including resistive contacts (20–5000 Ω range)
  • Phase-to-phase comparison: detect switching time asymmetry between phases in a single measurement
  • On-site reporting: print report immediately and export via USB to PC
  • Documentation and archiving: up to 200 measurement results stored internally for audits and quality records

When to choose CIBRE-L6 over CIBRE-L3?

The CIBRE-L3 has 3 contact inputs and is suitable for single-phase breakers and smaller applications. The CIBRE-L6 has 6 contact inputs and measures all three phases of a three-phase circuit breaker in one run — without re-connecting between phases. This saves measurement time and increases repeatability. For substation and high-voltage work, the L6 is the standard choice.

Key features

  • 6 dry contact inputs — simultaneous measurement of all three phases of a three-phase circuit breaker
  • Timing accuracy: ±0.05% rdg ± 0.1 ms over time windows of 1 s, 10 s, and 20 s
  • Contact detection: closed ≤20 Ω / open ≥5000 Ω; resistance range 20–5000 Ω
  • Trigger: internal or external; trigger input 24–300 V DC or ACpeak
  • Initiate output: 20 A, 300 V DC or ACpeak; current measurement 0–20 A DC, bandwidth 5 kHz
  • 4.3″ colour touchscreen — readable in direct sunlight, intuitive menu
  • Integrated 2.25″ thermal printer — print report on-site immediately
  • Memory: up to 200 measurement results stored internally
  • Communication: USB-A (export) + USB-B (PC); optional Bluetooth
  • Power supply: 100–240 V AC, 47/63 Hz — universal mains voltage
  • Battery option: 14.4 V Li-ion smart 3.45 Ah — field use without mains power
  • Protection class: IP67 (case closed) — robust for field and outdoor use
  • Operating temperature: −10 °C to +60 °C; storage −30 °C to +70 °C
  • Included: complete cable set, earth cable, USB stick, printer paper, digital manual, carry bag

Related products

  • CIBRE-L3 — entry-level variant with 3 contact channels for single-phase breakers
  • ARES 200D — contact resistance measurement (micro-ohm) as complement to contact timing
  • SUWI-120 (rental) — available for rental — substation tester for broader substation commissioning
  • TRAN-203 (rental) — available for rental — three-phase transformer analyser as supplementary system

Frequently asked questions

Which standards does the CIBRE-L6 cover?
IEC 62271-100 and IEEE C37.09 for contact timing of circuit breakers. For specific standards advice, we refer you to a qualified inspection authority.

Can I measure all three phases simultaneously?
Yes. The CIBRE-L6 has 6 contact inputs and measures phases A, B, and C of a three-phase circuit breaker in one run — including resistive contacts per phase.

Does the CIBRE-L6 operate without mains power?
Yes, with the optional Li-ion battery (14.4 V, 3.45 Ah). The IP67 case is fully equipped for field use.

Which software is used for reporting?
The CIBRE-L6 works with DMP software from HighTest. Free after registering on our training platform.

What is the calibration interval?
IONIO recommends 12 months. You receive an automatic reminder 6 weeks before expiry via our ERP system.

Difference between CIBRE-L6 and CIBRE-L3?
Choose L6 for three-phase circuit breakers: 6 channels measure all three phases simultaneously without re-connecting. The L3 is suitable for single-phase breakers or smaller applications.

Answer your questions

Are your test systems calibrated upon delivery?

What is the delivery time of your systems?

What is the warranty period you offer?

Do you also provide training sessions?

Do you also provide service?

What are the possible costs for software updates?

Are there licence fees for the software?

Do you calibrate test and measurement systems?

Can IONIO advise me which standard to apply?

Is a high-voltage test dangerous?

What is a hipot test

Gijsbert from IONIO will be happy to help.

At IONIO, we not only supply advanced testing and measurement systems, but also offer clear and expert advice to optimise the testing of your product. Find out how we can improve your business processes. A consultation can be scheduled in no time!

Nefit logo - klant van IONIO
Lixerio logo - klant van IONIO
Modular Lighting Instruments logo - klant van IONIO
Quooker logo - klant van IONIO
Deltalight logo - klant van IONIO
Bos Nieuwkoop logo - klant van IONIO
PITT cooking logo - klant van IONIO
Novy
TVH logo - klant van IONIO