CIBRE-30 series – 3-contact Circuit Breaker Analyser with motion analysis
The CIBRE-30 is a complete circuit breaker analyser for single-phase and single-pole-at-a-time measurements on LV, MV, and HV breakers. Three dry contact inputs measure both main and insertion resistor contacts. Motion analysis (speed, stroke, bounce) via linear or rotary encoder, plus voltage inputs on auxiliary contacts and coil current logging. With 7-inch touchscreen, built-in 2.28-inch printer, and optional Li-ion battery, the CIBRE-30 is fully field-ready in an IP67 case.
Applications
- Periodic inspection of MV and HV circuit breakers: contact timing, motion, and coil current in a single test session
- Commissioning of vacuum, SF6, oil, and air breakers single-pole
- Factory Acceptance Test at switchgear manufacturers with digital reporting via DMP software
- Maintenance interval monitoring in accordance with IEC 62271-100 and IEEE C37.09
Key features
- 3 dry contact inputs with detection of main and insertion resistor contacts
- Contact timing for O, C, O-C, C-O, and O-C-O operating sequences
- Motion analysis: Transducer Speed, Stroke, and Bounce
- Optional: linear encoder 325 mm or rotary encoder
- Voltage input V1 (analogue 0–250 V DC or ACpeak) and V2 (presence/absence 24–300 V DC or ACpeak)
- Coil current measurement 0–20 A DC, bandwidth 5 kHz
- Timing accuracy 0.05% rdg ± 0.1 ms across time windows of 1 s, 10 s, and 20 s
- 7-inch TFT colour touchscreen, readable in direct sunlight
- Built-in 2.28-inch thermal printer plus storage on USB and internal memory (200 records)
- Optional Bluetooth for wireless data transfer
- Optional Li-ion battery 14.4 V / 6.9 Ah for off-grid field work
- Protection class IP67 (case closed), operating temperature −10 to +60 °C
Which model fits your application?
Choose the CIBRE-30 if you measure pole-by-pole or work on single-phase circuit breakers and want to analyse not just contact timing but also the mechanical side (speed, stroke, bounce) and coil current. For simultaneous measurements on all three phases of a three-phase breaker in one run, the CIBRE-60 is the right choice.
If you do not need motion analysis and only want to measure contact timing, the lighter CIBRE-L3 is a more efficient choice (3 kg, 4.3-inch display). For additional contact resistance measurements in micro-ohm range, the ARES-200D is a logical complement.
Frequently asked questions about the CIBRE analyser series
Which standards do the CIBRE analysers cover?
What is the difference between CIBRE-30 and CIBRE-60?
What is the difference compared to the CIBRE-L3 / CIBRE-L6 timer series?
Does the CIBRE analyser operate without mains power?
Which encoder should I choose: linear or rotary?
Which software is used for reporting?
What is the calibration interval?
Can I measure contact timing and motion analysis simultaneously?
Which breaker types does the CIBRE analyser support?
What is the warranty and delivery time?
Do you also offer training and installation?
Gijsbert from IONIO will be happy to help.
At IONIO, we not only supply advanced testing and measurement systems, but also offer clear and expert advice to optimise the testing of your product. Find out how we can improve your business processes. A consultation can be scheduled in no time!