Home / Products / Cibre 60 Series 6 Contact Circuit Breaker Analyser

CIBRE-60 series – 6-contact Circuit Breaker Analyser with motion analysis

The CIBRE-60 is the professional circuit breaker analyser for three-phase breakers in MV and HV installations. With six dry contact inputs you measure all three phases — including insertion resistor contacts — simultaneously in one run, without re-wiring between phases. Motion analysis via linear or rotary encoder, voltage inputs, and coil current logging. With 7-inch touchscreen, built-in printer, and optional Li-ion battery, fully field-ready in an IP67 case.

ConsultationRequest a quoteBrochure

Applications

  • Commissioning of three-phase circuit breakers: simultaneous contact timing of all three phases in one run
  • Periodic inspection in accordance with IEC 62271-100: documenting open and close times and detecting deviations
  • Factory Acceptance Test including motion analysis and coil current logging
  • Maintenance assessment of vacuum, SF6, oil, and air breakers in substations

Key features

  • 6 dry contact inputs — simultaneous measurements on phases A, B, and C, including insertion resistor contacts
  • Contact timing for O, C, O-C, C-O, and O-C-O operating sequences
  • Motion analysis: Transducer Speed, Stroke, and Bounce
  • Optional: linear encoder 325 mm or rotary encoder
  • Voltage input V1 (analogue 0–250 V DC or ACpeak) and V2 (presence/absence 24–300 V DC or ACpeak)
  • Coil current measurement 0–20 A DC, bandwidth 5 kHz
  • Timing accuracy 0.05% rdg ± 0.1 ms across time windows of 1 s, 10 s, and 20 s
  • 7-inch TFT colour touchscreen, readable in direct sunlight
  • Built-in 2.28-inch thermal printer plus storage on USB and internal memory (200 records)
  • Optional Bluetooth for wireless data transfer
  • Optional Li-ion battery 14.4 V / 6.9 Ah for off-grid field work
  • Protection class IP67 (case closed), operating temperature −10 to +60 °C

Which model fits your application?

Choose the CIBRE-60 for three-phase circuit breakers: six channels measure all three phases simultaneously without re-wiring between phases, saving measurement time and increasing repeatability. For substation and high-voltage work, the CIBRE-60 is the standard choice.

If you measure single-pole-at-a-time or work on single-phase breakers, the CIBRE-30 with the same functionality on three channels is sufficient. If you only need contact timing without motion analysis, choose the CIBRE-L6 (three-phase, 6 channels, timing only) or CIBRE-L3 (single-phase). For additional contact resistance measurements in micro-ohm range, the ARES-200D is a logical complement. For broader substation commissioning, the SUWI-120 (rental) is a suitable companion system.

Frequently asked questions about the CIBRE analyser series

Which standards do the CIBRE analysers cover?

What is the difference between CIBRE-30 and CIBRE-60?

What is the difference compared to the CIBRE-L3 / CIBRE-L6 timer series?

Does the CIBRE analyser operate without mains power?

Which encoder should I choose: linear or rotary?

Which software is used for reporting?

What is the calibration interval?

Can I measure contact timing and motion analysis simultaneously?

Which breaker types does the CIBRE analyser support?

What is the warranty and delivery time?

Do you also offer training and installation?

Gijsbert from IONIO will be happy to help.

At IONIO, we not only supply advanced testing and measurement systems, but also offer clear and expert advice to optimise the testing of your product. Find out how we can improve your business processes. A consultation can be scheduled in no time!

Nefit logo - klant van IONIO
Lixerio logo - klant van IONIO
Modular Lighting Instruments logo - klant van IONIO
Quooker logo - klant van IONIO
Deltalight logo - klant van IONIO
Bos Nieuwkoop logo - klant van IONIO
PITT cooking logo - klant van IONIO
Novy
TVH logo - klant van IONIO